Thông số kỹ thuật
range of product | PowerLogic PM700 | |
---|---|---|
device short name | PM710 | |
product or component type | Power meter |
power quality analysis | Total harmonic distortion | |
---|---|---|
type of measurement | Current Voltage Frequency Power factor total Apparent power total Active power total Reactive power total Apparent power per phase Active power per phase Reactive power per phase Energy | |
supply voltage | 125...250 V DC 115...415 V AC 45...65 Hz | |
network frequency | 45...65 Hz | |
maximum power consumption in VA | 5 VA | |
display type | Backlit LCD | |
display resolution | 6 lines | |
sampling rate | 32 samples/cycle | |
measurement current | 5 A 1 A | |
input type | Current 0.005...6 A (impedance <= 0.1 Ohm) | |
measurement voltage | 10…480 V AC 45...65 Hz phase to phase 10…277 V AC 45...65 Hz phase to neutral | |
measurement accuracy | Power 1 % Current 0.5 % 1...6 A Voltage 0.5 % 50...227 V Frequency 0.02 Hz 45...65 Hz Power factor 0.0034 1A to 6A and from -0.5 to +0.5 | |
accuracy class | Class 2 reactive energy conforming to IEC 62053-23 Class 1 active energy conforming to IEC 62053-21 | |
communication port protocol | Modbus 19.2 kbauds | |
communication port support | RS485 | |
data recording | Min/max of instantaneous values |
electromagnetic compatibility | Limits for harmonic current emissions: , conforming to IEC 61000-3-2 Conducted and radiated emissions: , conforming to EN 55011 class B Electrostatic discharge immunity test: , class III, conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields: , class III, conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test: , class III, conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test: , class III, conforming to IEC 61000-4-5 Conducted RF disturbances: , class III, conforming to IEC 61000-4-6 Immunity to impulse waves: , class III, conforming to IEC 61000-4-8 Immunity to microbreaks and voltage drops: , class III, conforming to IEC 61000-4-11 Limitation of voltage changes, voltage fluctuations and flicker in low-voltage: , conforming to IEC 61000-3-3 | |
---|---|---|
mounting mode | Flush-mounted | |
mounting support | Panel | |
type of installation | Indoor installation | |
overvoltage category | III | |
IP degree of protection | IP30 back: conforming to IEC 60529 IP52 front face: conforming to IEC 60529 | |
relative humidity | 95 % at 50 °C | |
pollution degree | 2 | |
ambient air temperature for operation | -5…50 °C | |
ambient air temperature for storage | -40…85 °C | |
operating altitude | 0...3000 m | |
standards | IEC 61010-1 UL 508 CSA C22.2 No 14 | |
product certifications | CE CULus | |
width | 96 mm | |
depth | 69 mm | |
height | 96 mm | |
net weight | 0.37 kg |
Sustainable offer status | Green Premium product | |
---|---|---|
EU RoHS Directive | Compliant EU RoHS Declaration | |
Circularity Profile |